Installation, Mounting the h, S transmitter – RKI Instruments 65-2424RK User Manual

Page 8

background image

4 • 65-2424RK H

2

S Transmitter

Installation

This section describes procedures to mount the H

2

S transmitter in the monitoring

environment and wire the transmitter to a gas monitoring controller.

Mounting the H

2

S Transmitter

1.

Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.

Select a site where the transmitter is not likely to be bumped or disturbed. Make
sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.

Select a site where the target gas is likely to be found first.

NOTE:

If your application does not require a specific mounting site, mount the
transmitter at approximately breathing level.

Figure 2: Mounting the H

2

S Transmitter

2.

Remove the enclosure’s cover by unscrewing the four cover screws, one at each
corner.

3.

At the monitoring site, use #6 screws through the enclosure’s two mounting holes to
secure it to a vertical surface.

4.

Secure the cover to the enclosure with the four cover screws.

1.50

.54

.24

2.52

H S Sensor

2

Cable Bushing

.80 max

2X, Accessible With Lid
Removed

Ø .160 mounting hole,

3.86

3.39

1.42