beautypg.com

Load application, Single phase load, Three phase load – Multiquip DCA125SSIU User Manual

Page 25

background image

DCA125SSIU 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #3 (01/13/11) — PAGE 25

LOAD APPLICATION

SINGLE PHASE LOAD

Always be sure to check the nameplate on the generator
and equipment to insure the wattage, amperage, frequency,
and voltage requirements are satisfactorily supplied by the
generator for operating the equipment.

Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require
130—150% more wattage than the rating on the nameplate,
as the wattage is infl uenced by the effi ciency, power factor
and starting system of the equipment.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below
when connecting loads.

Table 6. Cable Selection (60 Hz, Single Phase Operation)

Current

in

Amperes

Load in Watts

Maximum Allowable Cable Length

At 100

Volts

At 200

Volts

#10 Wire

#12 Wire

#14 Wire

#16 Wire

2.5

300

600

1000 ft.

600 ft.

375 ft.

250 ft.

5

600

1200

500 ft.

300 ft.

200 ft.

125 ft.

7.5

900

1800

350 ft.

200 ft.

125 ft.

100 ft.

10

1200

2400

250 ft.

150 ft.

100 ft.

15

1800

3600

150 ft.

100 ft.

65 ft.

20

2400

4800

125 ft.

75 ft.

50 ft.

CAUTION: Equipment damage can result from low voltage

NOTICE

If wattage is not given on the equipment’s name plate,
approximate wattage may be determined by multiplying
nameplate voltage by the nameplate amperage.

Table 5. Power Factor By Load

Type of Load

Power Factor

Single-phase induction motors

0.4-0.75

Electric heaters, incandescent lamps

1.0

Fluorescent lamps, mercury lamps

0.4-0.9

Electronic devices, communication
equipment

1.0

Common power tools

0.8

THREE PHASE LOAD

When calculating the power requirements for 3-phase
power use the following equation:

An inadequate size connecting cable which cannot carry the
required load can cause a voltage drop which can burn out
the appliance or tool and overheat the cable. See Table 6.

 When connecting a resistance load such as an

incandescent lamp or electric heater, a capacity of up to
the generating set’s rated output (kW) can be used.

 When connecting a fl uorescent or mercury lamp, a

capacity of up to the generating set’s rated output (kW)
multiplied by 0.6 can be used.

 When connecting an electric drill or other power tools,

pay close attention to the required starting current
capacity.

When connecting ordinary power tools, a capacity of up to
the generating set’s rated output (kW) multiplied by 0.8 can
be used.

NOTICE

Motors and motor-driven equipment draw much greater
current for starting than during operation.

NOTICE

If 3Ø load (kVA) is not given on the equipment
nameplate, approximate 3Ø load may be determined
by multiplying voltage by amperage by 1.732.

DANGER

Before connecting this generator to any building’s
electrical system, a licensed electrician must install
an isolation (transfer) switch. Serious damage to
the building’s electrical system may occur without this
transfer switch.