HU-224/225 humidity transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these humidity transducers with VDC output:

Wiring HU-224/225 Units with VDC Output

1. Remove the terminal block by carefully pulling it off the circuit board.
2. Locate the [+], [-] and [O] terminal markings on the board.
3. Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the negative output terminal.
4. Connect the [O] terminal, which is the positive VDC output terminal, to the controller’s input terminal.
5. Re-insert the terminal block to the circuit board and apply power to the unit.
6. Check the appropriate VDC output using a voltmeter set on DC volts across the [O] and [-] terminals.

TYPICAL APPLICATIONS (wiring diagrams)

Model HU-224/225

Technical Information

TI.224/225-08

HUMIDITY SENSOR

Page 3 of 4

HU-224

DUCT MOUNT

0 to 10 VDC (default)

0 to 5 VDC

HU-225

WALL MOUNT

0 to 10 VDC (default)

0 to 5 VDC

1

2

O N

1

2

O N

VDC Output

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Figures 3 & 4 illustrate typical wiring diagrams for the HU-224/225, 0–5/0–10 VDC output humidity transducers.

Figure 3 – Wiring for VDC Output when applied with External AC Supply.

Figure 4 – Wiring for VDC Output when applied with External DC Power Supply.

Signal

+

Common

Supply

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–40 VDC Power Supply

RoHS

0 to 10 VDC

(Factory Default)

1

2

O N

1

2

O N

HU-224 (Duct Mount)

Board Layout

HU-225 (Wall Mount)

Board Layout

0 to 10 VDC

(Factory Default)

Figure 5 – Dip Switch Settings for HU-224/225 VDC Output

S Z

ON

1

2

SPAN
ZERO

0

-

+

ZERO
SPAN

Z S

+

-

0

ON

1

2

This manual is related to the following products: