Software operation
User Interface Dialogs
Registry "Time Set" − Time Before Shutdown
l
14
LDCDP−EPC50ACU EN 4.0
2.3.3
Registry "Time Set" − Time Before Shutdown
ACU UPS Vx.x:
Dialog Box
Value Range
Explanation
Time Before Shutdown
0 ... 60 s
Period of time from identifying a mains failure by the ACU UPS
control unit until shutting down the IPC. This period of time
must be shorter than the delay time (
time needed by the IPC to shut down.
Example:
The IPC can be supplied for 100 s by the battery pack and needs
a maximum of 20 s for a safe shutdown.
Delay time = 100 s
Time before shutdown = < 80 s
2.3.4
Registry "Application"− Start External Programs
ACU UPS Vx.x:
While the ACU software counts down the seconds until the IPC is shut down after a voltage
failure, an external program can be started.
Dialog Box
Value Range
Explanation
Executable Application
−
Path of the executable program file of the application
[Browse]
−
Search executable program file
Execute Application
On/Off
On: The program file specified in "Executable Application" is
executed.