2 registry "acu control" - configure ups, Registry "acu control" − configure ups, Software operation – Lenze ACU UPS for Industrial PCs User Manual
Page 12

Software operation
User Interface Dialogs
Registry "ACU Control" − Configure UPS
l
12
LDCDP−EPC50ACU EN 4.0
2.3.2
Registry "ACU Control" − Configure UPS
)
Note!
This registry is only shown when the ACU software has been called up via the
system panel. It is not shown when the software is called up by double−clicking
the symbol in the information bar of the Windows task bar.
ACU USV V2.x:
Dialog Box
Value Range
Explanation
Buffer Time [s]
0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the
ACU UPS control unit. Thus, voltage fluctuations are filtered
out.
Delay Time
0 ... 240 s;
infinite
Maximum period of time the industrial PC can be fed by the
battery/capacitor pack, depending on the hardware.
Restart after Delay Time
On/Off
On: Restart or shutdown of the system when the delay time is
up.
UPS Activated
On/Off
On: UPS support activated
Off: UPS support deactivated
Auto off after shutdown
On/Off
On: The ACU UPS control unit is switched off right after the
shutdown of the system. This function requires a system with
ACPI support (ETX−CD).
Backlight off after Power Fail
On/Off
On: Deactivates the backlight of the TFT display in case of a
voltage failure.