Drive control & communication, 25 rg-mcmod – Lenze MC Series Drives Modbus Communications User Manual
Page 29

25 RG-MCMOD
Drive Control & Communication
AC Tech
Register
Number
(hexadecimal
representation)
Parameter
1
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory Default
103 (67)
104 (68)
105 (69)
52
3,4
53
3,4
54
3,4
TB14OUT
TB15OUT
RELAY
00 - None
01 - Run
02 - Fault
03 - /Fault
04 - Lock
05 - @ Speed
06 - Above #3
07 - I Limit
08 - Auto/Man
09 - Follower Present
10 - Min/Max
11 - /Min/Max
12 - Min Alarm
13 - /Min Alarm
14 - Max Alarm
15 - /Max Alarm
16 - Reverse
17 - Sleep
18 - SPD = 0Hz
00 - None
106 (6A)
55
3,4
TB5B LOSS
00 - Fault
01 - SP#4
02 - None
00 - Fault
108 (6C)
57
SERIAL
00 - Disable
01 - w/ Timer
02 - w/o Timer
00 - Disable
109 (6D)
58
ADDRESS
1 - 247
30
112 (70)
61
PASSWORD
0000 - 9999
0019
114 (72)
63
SOFTWARE
(View Only)
(N/A)
115 (73)
64
MONITOR
00 - OFF
01 - ON
01 - ON
116 (74)
65
PROGRAM
00 - Maintain
01 - Reset 60
02 - Reset 50
Refer to Note 10
01 - Reset 60
117 (75)
66
HISTORY
00 - Maintain
01 - Clear
00 - Maintain
121 (79)
70
3,4
PID MODE
00 - Off
01 - Normal
02 - Reverse
00 - Off
125 (7D)
74
3,4
PID FB
00 - TB-5A
01 - TB-5B
00 - TB-5A
126 (7E)
75
3,4
FB @ MIN
0 - 65000
0 (0.0%)
127 (7F)
76
3,4
FB @ MAX
0 - 65000
65000 (100%)
129 (81)
78
3,4
I GAIN
0 - 100 (0.0 - 10.0 sec)
0 (0.0 sec)
130 (82)
79
3,4
D GAIN
0 - 100 (0.0 - 10.0 sec)
0 (0.0 sec)
131 (83)
80
3,4
PID ACC
0 - 1000 (0.0 - 100.0 sec)
300 (30.0 sec)
132 (84)
81
3,4
MIN ALRM
FB @ MIN - FB @ MAX
0.0%
133 (85)
82
3,4
MAX ALRM
FB @ MIN - FB @ MAX
0.0%
149 (95)
69
2
98
LANGUAGE
Refer to Note 11
English
150 (96)
70
2
99
3,4
FAULT HISTORY
(View Only)
(N/A)
1 = Drive's programming parameter number; 2 = MC1000 without PID (SW ver 213-083, rev 13 or older); 3 = MC1000 with PID; 4 = MC3000