Drive control & communication, 2 parameter list – Lenze MC Series Drives Modbus Communications User Manual
Page 25

21 RG-MCMOD
Drive Control & Communication
6.2 Parameter List
AC Tech
Register
Number
(hexadecimal
representation)
Parameter
1
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory Default
51 (33)
0
LINE VOLTS
00 - High
01 - Low
02 - Auto
02 - Auto
52 (34)
1
SPEED #1
Min. Freq - Max. Freq (0.00 - 120.00 Hz)
2000 (20.00 Hz)
5
53 (35)
2
SPEED #2
Min. Freq - Max. Freq
2000 (20.00 Hz)
5
54 (36)
3
SPEED #3
Min. Freq - Max. Freq
2000 (20.00 Hz)
5
55 (37)
4
SPEED #4
Min. Freq - Max. Freq
2000 (20.00 Hz)
5
56 (38)
5
SKIP #1
MC1: 0 - 65000 (.00 - 650.00 Hz)
MC3: 0 - Max Freq (.00 Hz - Max. Freq)
0 (.00 Hz)
5
57 (39)
6
SKIP #2
MC1: 0 - 65000 (.00 - 650.00 Hz);
MC3: .0 - Max Freq (00 Hz - Max. Freq)
0 (.00 Hz)
5
58 (3A)
7
BAND WID
0 - 1000 (.00 - 10.00 Hz)
100 (1.00 Hz)
5
59 (3B)
8
ACCEL
Refer to Note 4
300 (30.0 sec)
60 (3C)
9
DECEL
Refer to Note 5
300 (30.0 sec)
61 (3D)
10
MIN FREQ
0 - Max Frequency (0.00 - 120.00 Hz)
50 (.50 Hz)
5
62 (3E)
11
MAX FREQ
Min Frequency - 12000 (120.00 Hz) Note 6
6000 (60.00 Hz)
5
63 (3F)
12
DC BRAKE
Refer to Note 7
0 (.0 VDC)
64 (40)
13
DC TIME
0 - 9999 (.0 - 999.9 sec)
0 (.0 sec)
65 (41)
14
DYN BRAKE
00 - Off
01 - On
00 - Off
67 (43)
16
CURRENT
25 - 180 (25 - 180%), Refer to Note 8
180 (180%)
68 (44)
17
MOTOR OL
25 - 100 (25 - 100%)
100 (100%)
69 (45)
18
BASE
2000 - 36000 (20.00 - 360.0 Hz)
6000 (60.00 Hz)
5
70 (46)
19
FX BOOST
0 - 300 (0.0 - 30.0%)
Refer to Note 9
71 (47)
20
2,3
AC BOOST
0 - 200 (0.0 - 20.0%)
0 (.0%)
72 (48)
21
2,3
SLIP CMP
0 - 50 (0.0 - 5.0%)
0 (.0%)
73 (49)
22
TORQUE
00 - Contant
01 - Variable
02 - CT/NOCMP
00 - Constant
74 (4A)
23
CARRIER
00 - 2.5 kHz
01 - 6 kHz
02 - 8 kHz
03 - 10 kHz
04 - 12 kHz
05 - 14 kHz
00 - 2.5 kHz
1 = Drive's programming parameter number; 2 = MC1000 without PID (SW ver 213-083, rev 13 or older); 3 = MC1000 with PID; 4 = MC3000; 5 = Hundredths place