EDKRBG018R DE/EN/FR/ES/IT 8.0
4
Technical data
4.1
General data and operating conditions
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
EAC
TP TC 020/2011
(TR CU 020/2011)
Electromagnetic
compatibility of
technical means
Eurasian Conformity
TR CU: Technical Regulation
of Customs Union
EAC
TP TC 004/2011
(TR CU 004/2011)
On safety of low
voltage equipment
Eurasian Conformity
TR CU: Technical Regulation
of Customs Union
Approval
UR
UL508
Industrial Control Equipment, Underwriter
Laboratories (File−No. E221095) for USA and Canada
Protection of persons and equipment
Enclosure
EN 60529
IP20
NEMA 250
Protection against
contact to type 1
Thermal contact
Design
NC contact, 100 °C
Switching capacity
250 V AC / 2.5 A
110 V AC / 1.6 A
Environmental conditions
Climate
Storage
IEC/EN 60721−3−1
1K3 (−25 ... +60 °C)
Transport
IEC/EN 60721−3−2
2K3 (−25 ... +70 °C)
Operation
IEC/EN 60721−3−3
3K3 (−10 ... +55 °C)
Current derating from +45 ... +55 °C: 1 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating 5 %/1000 m
Vibration resistance
(9.81 m/s
2
= 1 g)
EN 50178,
IEC 61800−5−1,
Germanischer
Loyd, general
conditions