Appendix, Application example – Lenze EPM−H606 User Manual
Page 105

Appendix
Application example
EPM−H605 with safety PLC and EVS 93xx − ES V004 servo inverter
10
l
105
EDBPM−H605 DE/EN/FR 7.2
10
Appendix
10.1
Application example
10.1.1
EPM−H605 with safety PLC and EVS 93xx − ES V004 servo inverter
ƒ
The safe PLC takes over the entire drive control.
ƒ
The safe sensor technology is supplied by the clock outputs of the safe
PLC and is applied to the safe digital inputs of the PLC.
ƒ
Safety relay K
SR
and mains contactor K10 are used to safely disconnect
the motor torque.
ƒ
Two proximity switches and a safe evaluator are used to safely monitor
the speed.
ƒ
Operating mode "manual" is used to monitor a reduced speed. Keep the
confirmation key pressed to enable the motion process.
ƒ
The PLC uses a safe output to change the speed limit of the speed
monitor.
ƒ
The speed monitor switches off its outputs when the limit speed is
exceeded.