Product description, Warnings – Lenze MC−xxx Card User Manual
Page 18

Product description
Variants
MC−PBM, MC−PBS
l
18
BA_MC−Card EN 1.0
Technical data
MC−PBM, MC−PBS
Conformity, approval, directive
Conformity
CE
EN 61000−6−4
EN 61000−6−2
EMC Directive Class A,
industrial premises
Approval
UR
UL 508
CSA C22.2
Process Control Equipment
(File−No. E236341)
Directive
RoHS
−
Products lead−free in accordance with CE
Directive 2011/65/EU
General data and operating conditions
See standard device
Electrical data
Current
< 0.2 A
at standard device supply voltage of 24 V
Electrical isolation to the
fieldbus
yes
Mechanical data
Mass
< 0.1 kg
Communication
Type
PROFIBUS−DP, ISO 7498
Protocol
PROFIBUS−DP
Topology
Line, system
Node
MC−PBM (Master) / MC−PBS (Slave)
Max. number of nodes per
segment
max. 32
Max. number of nodes per
system
max. 128
Baud rate
^ 24
Bus length
¸
O
Warnings!
Use only together with appropriate cable connectors, provided with screws for
securement and secure connector to avoid loosening.
For use in controlled environment only.
¹
O
Warnings!
A utiliser exclusivement avec des connecteurs de câble à vis adaptés. Fixer les
connecteurs pour éviter toute déconnexion.
Destiné uniquement à des zones à environnement contrôlé.