Configuration – Lenze EVF9383 User Manual
Page 83

Configuration
2−75
l
EDSVF9383V−EXT EN 2.0
CONV3
CONV3
CONV3−OUT
CONV3−IN
C0953
C0952
C0950
C0951
Fig. 2−59
Conversion (CONV3)
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
CONV3−IN
phd
C0953
dec [rpm]
C0952
4
1000
CONV3−OUT
a
−
−
−
−
−
Limited to ±199.99 %
This FB is used to convert speed signals into analog signals. The conversion is done according to
the formula:
CONV3−OUT
+ CONV3−IN @ 100 %
15000 rpm
@ C0950
C0951
CONV4
CONV4
CONV4−OUT
CONV4−IN
C0958
C0957
C0955
C0956
Fig. 2−60
Conversion (CONV4)
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
CONV4−IN
phd
C0958
dec [rpm]
C0957
4
1000
CONV4−OUT
a
−
−
−
−
−
Limited to ±199.99 %
This FB is used to convert speed signals into analog signals. The conversion is done according to
the formula:
CONV4−OUT
+ CONV4−IN @ 100 %
15000 rpm
@ C0955
C0956
CONV5
CONV5
CONV5−OUT
CONV5−IN
C0658
C0657
C0655
C0656
Fig. 2−61
Conversion (CONV5)
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
CONV5−IN
a
C0658
dec [%]
C0657
1
1000
CONV5−OUT
phd
−
−
−
−
−
Limited to ±29999 rpm
This FB is used to convert analog signals into speed signals. The conversion is done according to
the formula:
CONV5−OUT
+ CONV5−IN @
15000 rpm
100 %
@ C0655
C0656