Electrical installation
Connection data
l
46
EDKZN3B045 DE/EN/FR 3.0
4.3
Connection data
[mm
2
]
[AWG]
[mm]
[Nm]
[
lb−in
]
EZ...0120H012
0.2 ... 4
0.25 ... 4
0.5 ... 1.5
24 ... 10
8
0.6 ... 0.8
5.3 ... 7.1
EZ...0088H024
0.2 ... 6
0.25 ... 6
0.5 ... 4
24 ... 8
9
1.5 ... 1.8
13.2 ... 15.9
EZ...0055H045
0.5 ... 16
0.5 ... 6
20 ... 4
16
2 ... 2.3
17.7 ...
20.35
EZ...0055H045U
4.4
Mounting steps
Design 1
ƒ
EZN3A0120H012
ƒ
EZN3A0088H024
EZN−075a
How to wire the filter:
1. Deenergise the control cabinet and fuse it against re−energisation.
2. Connect the connection cables of the standard device to terminal "Load"
2.
–
Observe the documentation of the standard device!
3. Connect the mains cables to terminal "Line"
0.
–
Observe tightening torque!
This manual is related to the following products: