7 troubleshooting and fault elimination, 1 status of the drive, Troubleshooting and fault elimination – Lenze E931Ex User Manual
Page 38: Status of the drive, 7troubleshooting and fault elimination
Troubleshooting and fault elimination
Status of the drive
7
l
38
GHB 13.0001−EN EN 3.0
7
Troubleshooting and fault elimination
7.1
Status of the drive
The current operating status of the drive controller is displayed by 3 light−emitting diodes.
Thus, a quick diagnostics is possible. Details with regard to diagnostics information are
supplied by the parameterisation software.
LED
Colour
State
Note
State
Green
on
The control is correctly supplied by a 24 V control voltage, the drive is ready for operation.
blinking
Data is written on or read from the memory card.
off
No voltage
Power
Yellow
on
The power section is enabled, the motor is supplied with voltage. The drive works with the set
control.
off
The drive does not work, the output stage is inactive.
Error
Red
off
No fault
blinking
Internal drive error
1)
After the cause of the error has been eliminated, you have to acknowledge the error message:
l
Either by using the parameterisation software, or via an edge at DIN9 (controller enable).
l
If no error is active anymore, the LED goes out.
Green
Yellow
Red
on
l
The drive is in the initialisation phase after the control voltage has been switched on.
l
A new firmware is being installed.
1)
Detailed description of the blink codes:
^ 40
)
Note!
The light−emitting diode "Error" constantly blinks if a fault is active:
ƒ
It only displays one fault at a time.
ƒ
If several faults are active at the same time, the fault that occured first is
displayed.