3 technical data, 1 general data and operating conditions, Technical data – Lenze E931Ex User Manual
Page 15: General data and operating conditions, 3technical data

Technical data
General data and operating conditions
3
l
15
GHB 13.0001−EN EN 3.0
3
Technical data
3.1
General data and operating conditions
Conformity
CE
2006/95/EC
Low-Voltage Directive
Regulations
EN 61800−3
Interference level B
Climatic conditions
Air humidity max. 90 % without condensation
Cooling
Passively via housing surface and rear panel
Admissible temperature range
Transport
−25 °C... +70 °C
Storage
−25 °C... +70 °C
Operation
0 °C ... +50 °C
above +40 °C, reduce the power by 20 W/°C
Permissible installation height
0 ... 1000 m amsl
above 1000 m amsl, reduce the rated output
current by 5 %/1000 m
Mounting position
Vertical
Installation clearances
above/below
³ 100 mm
sidewise
Directly alignable
Monitoring
Overvoltage / undervoltage in the DC bus, overcurrent or short
circuit of the output stage, motor temperature and output stage
temperature, I
2x
t−monitoring of the motor, encoder monitoring
Type of protection
IP 20
Inputs
6 digital inputs, 2 analog inputs
(adjustable via software)
Outputs
2 digital outputs, 2 analog outputs
(adjustable via software)
Memory cards
Multimedia card