Commissioning
Setting node address and baud rate
EDK82ZAFUC−001 DE/EN/FR 4.0
66
l
H2_set_node_addr_baud−Ueb−rate Hinweis
Setting node address and baud rate
)
Note!
Node address and baud rate can be set via DIP switches or codes.
ƒ
Select an unambiguous node address between 1 and 63 for each device.
ƒ
The baud rate must be set to the same value for all controllers and the
master computer.
ƒ
If the DIP switches S1 ... S7 are in OFF position, the code settings for node
address/baud rate are active. If a DIP switch is set to ON, the node address
(C1509)/baud rate (C1516) will be overwritten with the corresponding
values of the switch positions.
Settings via codes
ƒ
DIP switches S1 ... S7 = OFF (Lenze setting)
ƒ
Set the node address via C1509.
ƒ
Set the baud rate via C1516.
Settings via the DIP switches at the front
ƒ
Set the node address via DIP switches S1 ... S7.
ƒ
Set the baud rate via DIP switches S8 ... S10.
Accepting changed settings
ƒ
Switch off the voltage supply of the function module and the controller
and then switch it on again to activate the changed settings.