Protective insulation, Connection terminals, Technical data – Lenze E82ZAFUC001 User Manual
Page 49
![background image](/manuals/565938/49/background.png)
Technical data
Protective insulation
EDK82ZAFUC−001 DE/EN/FR 4.0
49
l
H2 Schutzisolierung−klemmbesch−001
Protective insulation
Insulation between bus and ...
Type of insulation (in accordance with EN
61800−5−1)
l
Power stage
– 8200 vector
Reinforced insulation
– 8200 motec
Reinforced insulation
– starttec
Reinforced insulation
l
Reference earth / PE (X3/7)
Functional insulation
l
External supply (X3/59)
Functional insulation
l
Supply for CINH (X3/20)
Functional insulation
l
Controller inhibit, CINH (X3/28)
Functional insulation
Connection terminals
Terminal
X3/
Designation
Function / level
CG
CAN−GND
Reference potential for CAN
CL
CAN−LOW
CAN data line (LOW)
CH
CAN−HIGH
CAN data line (HIGH)
59
External DC voltage supply for the function module:
l
24 V DC (21.4 V DC − 0 % ... 28.8 V DC + 0 %)
l
Current consumption at 24 V DC: 80 mA
The current flowing to other nodes via clamp 59 when looping
through the supply voltage must not exceed 3 A.
7
GND1
Reference potential for X3/20 and X3/59
39
GND2
Reference potential of controller inhibit (CINH) at X3/28
28
CINH
Controller inhibit
l
Input resistance: 3.3 k
W
l
Start = HIGH (+12 ... +30 V DC)
l
Stop = LOW (0 ... +3 V DC)
(reference: GND2)
20
DC voltage source for the external supply of controller inhibit (CINH)
l
+20 V DC (reference: GND1)
l
I
max
= 10 mA