Commissioning – Lenze EMF2179IB User Manual
Page 71

Commissioning
Enabling the standard device via the communication module
EDKMF2179 DE/EN/FR 4.0
71
l
H2_FirstOn−unkontroll_Anlauf
Enabling the standard device via the communication module
)
Note!
ƒ
Plugging the communication module into another controller during
operation may result in undefined operating states.
ƒ
Lenze codes in the standard device and the communication module can be
read and written via the manufacturer−specific class "110".
ƒ
Current program examples can be found on the Internet in the ˜Services &
Downloads˜ area at
http://www.Lenze.com
82XX / 8200 vector frequency inverters
Step
Procedure
Comments
1.
Set C0001 from
"0" to "3"
The Lenze parameter C0001 (operating mode) can be set via the XT
keypad or directly via DeviceNet.
Example of direct setting via DeviceNet:
Write (C0001 = 3)
l
Class: 0x6E (110
dec
)
l
Instance: 0x1
l
Attribute: 0x1
l
Service code: Set Single Attribute
l
Data send: 0x7530 (30000
dec
)
2.
Set terminal 28 to
HIGH level
Terminal 28 (controller enable) is always active and has to be on
HIGH level during DeviceNet operation. Otherwise the controller
cannot be enabled via DeviceNet.
3.
Set input terminal
for QSP to HIGH level
The QSP function (quick stop) is always active. If QSP is configured to
an input terminal (Lenze setting: not assigned), it has to be on HIGH
level during DeviceNet operation.
4.
The controller now accepts parameter and process data.