Process data transfer
Lenze device control
Process data transfer
l
35
EDS82ZAFIC EN 2.0
Selection of setpoint source
8200 vector / 8200 motec controller
For these controllers, the selection of the setpoint source is defined using code C0001
(index: 0x5FFE). For evaluating the process data, the code C0001 has to be set to the
value "3" when the controller is operated with the function module. The setpoint source is
provided by the process data channel which describes the frequency setpoint (mapping to
C0046) and the control word (C0135).
In C0412/x, the assignment of the setpoint source to the desired analog signal can be
checked / changed.
)
Note!
The selection of the setpoint source (C0001) must be set identically in all
parameter sets used in the controller.