Commissioning – Lenze E82ZAFPC010 User Manual
Page 37

Commissioning
Configuring the host system (master)
l
37
EDS82ZAFPC010 EN 4.0
Device data base file
The following configurations are saved in the device data base file LENZ00DA.GSE:
Modules in LENZ00DA.GSE
Parameter data
without/with consistency
Process data
without/with consistency
Assigned
I/O memory
Without
With
Without
With
PAR (Cons.)
+ PZD (n Words)
·
n words
4 + n words
PAR (Cons.)
+ PZD (n Words Cons.)
·
n words
4 + n words
PAR
+ PZD (n Words)
·
n words
4 + n words
PZD (n Words)
Without parameter data channel
n words
n words
PZD (n Words Cons.)
Without parameter data channel
n words
n words
n = 1 ... 10
)
Note!
Device control via FIF status/control word
Device control is only possible if the DRIVECOM status machine (Lenze setting)
is switched off.
ƒ
Set C1510 /1 (PIW1) to the value 1":
FIF status word 1 (FIF−STAT1).
ƒ
Set C1511 /1 (POW1) to the value 1":
FIF control word 1 (FIF−CTRL1).
ƒ
Set C1512 to 65535" to reenable process output words.
For Lenze codes see (
¶ 69)
I
Tip!
Use overall consistency
ƒ
We recommend to use exclusively configurations with consistency for the
parameter data channel to avoid data conflicts between PROFIBUS−DP
master and host CPU.
ƒ
Please note that the processing of consistent data varies between hosts.
This must be considered in the PROFIBUS−DP application program.
ƒ
Detailed description of consistency: (
¶ 87)