Installation, Electrical installation terminal assignment – Lenze E82ZAFPC010 User Manual
Page 29

Installation
Electrical installation
Terminal assignment
l
29
EDS82ZAFPC010 EN 4.0
E82ZAFPC010 function module
GND1
GND1
B
7
20
59
+20V
A
28
39
7
GND2
X3.1
X3.2
X3.3
T/R(A)
T/R(B)
E82ZAFP011
Terminal
X3.1/
Designation
Function / level
+
PES
Additional HF shield termination
A
T/R(A)
RS485 data line A
B
T/R(B)
RS485 data line B
Terminal
X3.2/
Designation
Function / level
59
External DC voltage supply for the function module
l
+24 V DC
± 10% (reference: GND1)
l
Current consumption on 24 V DC: 80 mA
The current for looping through the supply voltage to other nodes via
terminal 59 must be max. 3 A.
7
GND1
Reference potential for X3.3/20
Terminal
X3.3/
Designation
Function / level
7
GND1
Reference potential for X3.3/20
39
GND2
Reference potential for controller inhibit (CINH) at X3.3/28
28
CINH
Controller inhibit
l
Input resistance: 3.3 k
W
l
Start = HIGH (+12 ... +30 V)
l
Stop = LOW (0 ... +3 V)
(reference: GND2)
20
DC voltage source for external supply of controller inhibit (CINH)
l
+20 V (reference: GND1)
l
I
max
= 10 mA