Parameter data transfer
8
l
56
EDS82ZAFPC010 EN 4.0
8
Parameter data transfer
PROFIBUS transmits parameter data and process data between the host (master) and the
drives connected to the bus (slaves). Depending on their time−critical nature, the data are
transmitted via different communication channels.
ƒ
Parameter data are transmitted via the parameter data channel.
– DRIVECOM parameter data channel
– PROFIdrive parameter data channel (DP−V0 / DP−V1)
ƒ
The parameter data channel provides access to all Lenze codes.
ƒ
In general, the transfer of parameter data is not time−critical.
ƒ
Parameter data are, for instance, operating parameters, diagnostic information and
motor data.
)
Note!
Cyclic writing to codes via PROFIBUS is only permissible if the automatic
parameter set storage of the controller C0003 is deactivated (value 0).