3 drivecom status word, Drivecom status word, Process data transfer – Lenze E82ZAFPC010 User Manual
Page 53

Process data transfer
DRIVECOM control
DRIVECOM status word
l
53
EDS82ZAFPC010 EN 4.0
7.2.3
DRIVECOM status word
Bit
Meaning
0
Device status "Ready to switch on"
0
1
Status less than "Ready to switch on"
Status at least "Ready to switch on"
1
Device status "Switched on"
0
1
Status less than "Switched on"
Status at least "Switched on"
2
Device status "Operation enabled"
0
1
Status less than "Operation enabled"
Status "Operation enabled"
3
Device status "Fault"
0
1
No fault (TRIP)
Fault (TRIP) active
4
Status "Inhibit voltage" command
0
1
Command applied
Command not applied
5
Status "Quick stop (QSP)" command
0
1
Command applied
Command not applied
6
Device status "Switch−on inhibit"
0
1
Status "Switch−on inhibit" not active
Status "Switch−on inhibit" active
7
Collective warning
0
1
No warning
Warning (overtemperature) active
8
Collective message
Automatic setting and resetting of pulse inhibit (IMP) in the device status "Operation enabled".
Possible causes: Undervoltage, overvoltage or overcurrent
0
1
No message
Message IMP active
9
Bus access right
1 Always
10
Status speed/frequency deviation
0
1
RFG
on
tu RFG
off
RFG
on
= RFG
off
11
0
Status DRIVECOM speed limitation
Always
12
Mapping of FIF status word 1 (FIF−STAT1), bit 0 (DCTRL1−PAR−B0)
13
Mapping of FIF status word 2 (FIFSTAT2), bit 0 (DCTRL1−PAR−B1)
14
Mapping of FIF status word 1 (FIFSTAT1), bit 2 (MCTRL1−IMAX)
15
Mapping of FIF status word 1 (FIF−STAT1), bit 5 (PCTRL1−QMIN)