4 technical data, 1 general data, 2 operating conditions – Lenze E82ZAFPC010 User Manual
Page 15: Technical data, General data, Operating conditions, 4technical data

Technical data
General data
4
l
15
EDS82ZAFPC010 EN 4.0
4
Technical data
4.1
General data
Field
Values
Order designation
E82ZAFPC001 (coated)
E82ZAFPC010 (PT design)
PUO ID number
0x00DA
Communication profile
(DIN 19245 Part 1 and Part 3)
l
PROFIBUS−DP−V0
Communication medium
RS485
Drive profile
l
DRIVECOM profile "Drive technology 20" (can be switched off)
Network topology
l
Without repeaters: line
l
With repeaters: line or tree
PROFIBUS stations
Slave
Baud rate [kbps]
9.6 ... 12000 (automatic detection)
Process data words
1 ... 10 words
(16 bits/word)
DP user data length
1 ... 10 process data words +
4 parameter data words
Max. number of bus devices
l
Standard: 32 (= 1 bus segment)
l
With repeaters: 125
Max. cable length per bus
segment
1200 m (depending on the baud rate and cable type used)
External DC−voltage supply
+24 V DC ±10 %, max. 80 mA
4.2
Operating conditions
Ambient conditions
Climate
Storage
IEC/EN 60721−3−1
1K3 (−25 to +60 °C)
Transport
IEC/EN 60721−3−2
2K3 (−25 to +70 °C)
Operation
Corresponding to the data of the Lenze standard device used (see documentation
of the standard device).
Pollution
EN 61800−5−1
Degree of pollution 2
Degree of protection
IP20 (protection against accidental contact according to NEMA 250 type 1)