Electrical installation
6.1
Important notes
ƒ
Installation must
– always be in accordance with the operating conditions specified in the Technical
data (
¶ 36).
– be carried out to EN 60204−1.
ƒ
Please observe the following when selecting the cable type:
– The cables used must comply with the approvals required for the application (e. g.
VDE, UL etc.).
– Fuses and cable cross−sections must be dimensioned in accordance with the
specifications in the documentation for the basic device.
ƒ
The described EMC properties are provided if the following conditions are complied
with:
– The devices are mounted according to the arrangement concept described.
– The prepared cables are used and remain unchanged.
{
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Death or severe injuries when touching the power terminals.
Protective measures:
ƒ
Switch off the power supply and wait for at least three minutes before
working on the power terminals.
ƒ
Make sure that all power terminals are deenergised.