6 electrical installation, 1 important notes, Electrical installation – Lenze E94AZMP User Manual
Page 48: Important notes

Electrical installation
Important notes
6
48
EDK94AZMP DE/EN/FR/ES/IT 7.0
6
Electrical installation
6.1
Important notes
ƒ
Installation must
–
always be in accordance with the operating conditions specified in the
Technical data ( 38).
–
be carried out to EN 60204-1.
ƒ
Please observe the following when selecting the cable type:
–
The cables used must comply with the approvals required for the
application (e. g. VDE, UL etc.).
–
Fuses and cable cross-sections must be dimensioned in accordance with
the specifications in the documentation for the basic device.
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Death or severe injuries when touching the power terminals.
Protective measures:
ƒ
Switch off the power supply and wait for at least three minutes
before working on the power terminals.
ƒ
Make sure that all power terminals are deenergised.
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Death or severe injuries when the device is touched in the event
of a fault.
Protective measures:
ƒ
Implement the actions required in the EN 61800-5-1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor
diameter 10 mm
2
or PE conductor must be connected twice)