2 residual hazards, Residual hazards, Safety instructions – Lenze E94AZMP User Manual
Page 35

Safety instructions
Residual hazards
2
35
EDK94AZMP DE/EN/FR/ES/IT 7.0
2.2
Residual hazards
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Death or severe injuries when touching the power terminals.
Protective measures:
ƒ
Switch off the power supply and wait for at least three minutes
before working on the power terminals.
ƒ
Make sure that all power terminals are deenergised.
Warnings!
Conditions of Acceptability:
ƒ
The products covered by this report are only intended for use
with Power Conversion Equipment (inverters).
ƒ
Consideration shall be given to the field wiring leads. No strain
relief test was performed on the leads.
ƒ
The devices in this report are only evaluated for factory wiring
use.
ƒ
Temperature tests were performed with hook mounted drive.
Warnings!
Conditions d’acceptabilité :
ƒ
Les produits concernés par ce rapport sont destinés
exclusivement à être utilisés avec des convertisseurs de
puissance (variateurs ou power conversion equipment).
ƒ
Une attention particulière doit être apportée aux tresses de
câblage à pied d’oeuvre. Aucun test de décharge de traction n’a
été réalisé sur ces éléments.
ƒ
Les équipements concernés par ce rapport sont évalués
exclusivement pour un câblage en usine.
ƒ
Les tests de température ont été réalisés avec un entraînement à
crochet.