Instruction manual – model cf2300a oil burner, Verify firing rate, Verify air tube – Beckett CF 2300A User Manual
Page 5

Instruction Manual – Model CF2300A Oil Burner
5
Form 6104 BCF-23-R0399
Table 2 – Air tube capacity vs. firebox pressure
Figure 2 – Air tube mounting dimensions
2304
E
D
G
T
2°
1
F
E Insertion depth
G Air tube to inside of chamber
– 0.25" ± 0.125"
T Air tube length
D Tube diameter
Figure 1 – Min. combustion chamber dimensions
①
Install the burner with a 2° pitch as shown.
2305
A
L
❏
Verify firing rate
• Refer to appliance manufacturer’s instructions (if avail-
able) for firing rate and nozzle selection. Otherwise, the
maximum recommended firing rate for the burner depends
on the length of the firing chamber and the distance from
the burner center to the chamber floor. Verify that the cham-
ber dimensions are at least as large as the minimum values
given in
Figure 1
. If the appliance dimensions are smaller
than recommended, reduce the firing rate accordingly.
❏
Verify air tube
• The information in this section may be disregarded if the
air tube is supplied by the appliance manufacturer.
• Two tube arrangements are available –
Tube
KG
— 7.0 to 19.9 GPH per
Table 2
Tube
KS
— 10.0 to 19.9 GPH per
Table 2
• Maximum firing capacity depends on the firebox pressure.
Use
Table 2
to verify the correct air tube type for the firing
rate required. Use Tube
KS
only when Tube
KG
cannot
provide the firing rate required.
• See
Figure 2
to verify the correct air tube length and air
tube combination code.
Firing rate
Minimum dimensions
(refractory-lined)
(wet-base boilers)
A
L
A
L
5 to 10 gph
8.0"
35.0"
8.0"
40.0"
10 to 15 gph
9.0"
40.0"
9.0"
50.0"
15 to 20 gph
11.0"
55.0"
11.0"
60.0"
A.T.C. Codes
(A.T.C. = Air Tube Combination)
Tube KG
Tube KS
(Dim
T
)
(Dim
D
)
(Dim
F
)
(Dim
T
)
(Dim
D
)
(Dim
F
)
All —
6¹⁄₂
”
2¹⁵⁄₁₆
”
All —
8¹⁄₈
”
3¹¹⁄₁₆
”
6¾”
CF 66 KG
6¾”
CF 66 KS
—
—
8¾”
CF 86 KS
10¼”
CF 102 KG
11”
CF 110 KS
13¾”
CF 136 KG
14½”
CF 144 KS
17¾”
CF 176 KG
18½”
CF 184 KS
Firebox
pressure
(In. w.c.)
Tube KG
Tube KS
No reserve
air
10%
turndown
No reserve
air
10%
turndown
0.0
19.9 GPH
19.9 GPH
19.9 GPH
19.9 GPH
0.2
19.2 GPH
19.1 GPH
19.7 GPH
19.6 GPH
0.4
18.5 GPH
18.3 GPH
19.5 GPH
19.3 GPH
0.6
17.9 GPH
17.6 GPH
19.4 GPH
19.1 GPH
0.8
17.2 GPH
16.8 GPH
19.2 GPH
18.8 GPH
1.0
16.5 GPH
16.0 GPH
19.0 GPH
18.5 GPH
Note: 10% turndown indicates sufficient reserve air to reduce the CO
2
in the
flue to 90% of its value.
Note: The above ratings may vary 5% due to variations in actual job conditions.