beautypg.com

Pre-installation checklist, Instruction manual – model cf2300a oil burner, Combustion air supply – Beckett CF 2300A User Manual

Page 4: Clearances, Fuel supply, Vent system, Electrical supply, Verify burner components

background image

Instruction Manual – Model CF2300A Oil Burner

4

Form 6104 BCF-23-R0399

Pre-installation checklist

Table 1 – Nozzle capacities at various pressures

Combustion air supply

• The burner requires combustion air and ventilation air for

reliable operation. Assure that the building and/or com-
bustion air openings comply with National Fire Protection
Standard for Oil-Burning Equipment, NFPA 31. For appli-
ance/burner units in confined spaces, the room must have
an air opening near the top of the room plus one near the
floor, each with a free area at least one square inch per
1,000 Btu/hr input of all fuel burning equipment in the
room. For other conditions, refer to NFPA 31 (CSA B1139-
M91 in Canada).

• If there is a risk of the space being under negative pressure

or of exhaust fans or other devices depleting available air
for combustion and ventilation, the appliance/burner
should be installed in an isolated room provided with out-
side combustion air.

Clearances

• With the burner installed in the appliance, there must be

adequate space in front of and on the sides of the burner to
allow access and operation. Verify that the clearance di-
mensions comply with all local codes and with the appli-
ance manufacturer's recommendations.

Fuel supply

• The fuel supply piping and tank must provide #1 or #2

fuel oil at pressure or vacuum conditions suitable for the
fuel unit (oil pump) on the burner. Refer to fuel unit litera-
ture in the literature envelope in the burner carton to verify
allowable suction pressure.

When fuel supply is level with or higher than burner
fuel unit —
• When the fuel unit is not required to lift the oil, the instal-

lation is usually suitable for either a one-pipe or two-pipe
oil system. The oil pressure at the inlet of the fuel unit must
not exceed 3 psig.

• The fuel unit is shipped with the

by-pass plug

installed.

Leave the by-pass plug installed for all low/high firing
burners, regardless whether one-pipe (with by-pass loop)
or two-pipe
. See

Figure 8

for installation of the by-pass

loop required for one-pipe fuel supply installations. See

Figure 9

for connections to the fuel unit for two-pipe fuel

supply installations.

When fuel supply is below the burner fuel unit —
• Use a two-pipe oil system when the fuel unit must lift the

oil more than 8 feet if burner is equipped with a

B

fuel unit

— or more than 2 feet if burner is equipped with an

H

fuel

unit. The return line provided by the two-pipe system is
needed to purge the air from the fuel lines and minimize
the likelihood of air-related problems during operation.

Vent system

• The flue gas venting system must be in good condition

and must comply with all applicable codes.

Electrical supply

• Verify that the power connections available are correct for

the burner. All power must be supplied through fused dis-
connect switches.

Verify burner components —

Burner box

, Model CF2300A

Air tube assembly

(selected per following)

Mounting flange kit

Pedestal mounting assembly kit

(recommended)

Oil nozzle

, per

Table 1

— Use only 45° to 70° solid pat-

tern nozzles unless otherwise shown by appliance manu-
facturer.
Find the required firing rate in the 300 psig column (high
fire rate).
Select the corresponding nozzle from column 1 (Rated
gph @ 100 psig
).

Rated
gph @

100 psig

Pressure - pounds per square inch

125

150

175

250

275

300

4.50

5.04

5.51

5.95

7.11

7.46

7.79

5.00

5.59

6.12

6.61

7.91

8.29

8.66

5.50

6.15

6.74

7.28

8.70

9.12

9.53

6.00

6.71

7.35

7.94

9.49

9.95

10.39

6.50

7.27

7.96

8.60

10.28

10.78

11.26

7.00

7.83

8.57

9.26

11.07

11.61

12.12

7.50

8.39

9.19

9.92

11.86

12.44

12.99

8.00

8.94

9.80

10.58

12.65

13.27

13.86

9.00

10.06

11.02

11.91

14.23

14.92

15.59

10.00

11.18

12.25

13.23

15.81

16.58

17.32

11.00

12.30

13.47

14.55

17.39

18.24

19.05

12.00

13.42

14.70

15.87

18.97

19.90

20.78