beautypg.com

Technical data, Approvals/approval marks – JUMO 60.1540 Flue gas temperature monitor, STM-RW-2 Data Sheet User Manual

Page 2

background image

2013-04-09/00073204

Data Sheet 601540

Page 2/4

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

Technical data

Approvals/Approval marks

Electrical data

STM-RW-2

STM-RW-2/OS (729)

Switching element

Micro switch with change-over contact

Micro switch with 2 separate current circuits

1 x N/C contact and 1 x N/O contact

maximum
permissible contact rating

AC 230 V +10%, 10 (2) A, cos

ϕ = 1 (0.6)

DC 230 V +10%, 0.25A

Contact reliability

To ensure high switching reliability, we recommend a minimum load of:

AC / DC 24 V, 20 mA

Rating surge voltage

2500 V (via the switching contacts 400 V)

Overvoltage category II

Required fusing, see maximum switching current

Operating data

Limit value range

+40 °C to +120 °C (factory-set to +100 °C)
+20 °C to +400 °C (factory-set to +120 °C)

Hysteresis

Limit value range

STM-RW-2

STM-RW-2/OS (729)

+40 °C to +120 °C
+20 °C to +400 °C

10 - 18 K
10 - 22 K

10 - 30 K
10 - 40 K

Switching point accuracy
referring to the switch-off
point

Limit value range

Scale beginning

Scale end

+40 °C to +120 °C
+20 °C to +400 °C

+0/-10 K
+0/-15 K

+0/-10 K
+0/-20 K

Time constant

Flue gas:

≤ 45 sec.

Average
ambient temperature influ-
ence

Switching point offset referring to the deviation of +22 °C ~ 0.07 K/K

Temperatures / Position

STM-RW-2

Permissible
ambient temperature

on the probe:

on the switch head:

max. +700 °C
max. +80 °C, min. -50 °C

Set point adjustment

after removal of the case lid via internal scale

Permissible storage tempera-
ture

max. +80 °C / min. -50 °C

Rated position

as per DIN 16257, NL 0 to NL 90 (different rated positions (NL) on request)

Case

Case

Aluminum die cast, surface with impact resistant textured paint; lid: RAL 7032, bottom section: RAL 7015

Cable inlet

clamping gland M 20 × 1.5

Protection class

EN 60 529-IP54

Weight

approx. 0.8 kg

Process connection

Connection type

"DZ“ G 1/2 (fixed hexagon with external thread G 1/2), material: Steel

Immersion tube

15 x 150 mm, Material: Steel

Approval marks

Inspection authority

Certificates / Inspection
number

Inspection basics

valid for

DIN EN 14597

DIN CERTCO / TÜV Süd

ATW 862

DIN EN 14597

STM-RW-2