Data Sheet 604100
Page 2/4
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone:
+49 661 6003-0
Fax:
+49 661 6003-607
E-mail:
Internet:
www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:
+44 1279 635262
E-mail:
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866
1-800-554-5866
Fax:
315-437-5860
E-mail:
Internet: www.jumousa.com
Switching function
Technical data
Electrical data
Safety temperature monitor
STW
If the probe line falls below the entered setpoint value over a length of 15 cm with 3 m, 30 cm with 6 m, and
40 cm with 12 m, then electrical circuit 1-2 is opened while electrical circuit 1-4 is closed due to the change-
over function. When the temperature rises, the microswitch is automatically switched back to its original posi-
tion.
If the measuring system is destroyed (i.e. if the expansion fluid escapes) the pressure in the diaphragm drops
and permanently opens electrical circuit 1-2 and closes electrical circuit 1-4.
Safety temperature limiter
STB
In the event of a temperature drop, the safety temperature limiter automatically locks and can only be
unlocked manually once the temperature has risen again.
If the measuring system is destroyed (i.e. if the expansion fluid escapes), the pressure in the diaphragm drops
and permanently opens electrical circuit 1-2 and closes electrical circuit 1-4.
Type 5
Type 7
Case
Case bottom section: PA (reinforced)
Color: Silver gray RAL 7001
Case lid: ABS with inspection window (PMMA)
Color: Cobalt blue RAL 5013
Setpoint value adjustment
STW, STB The switching point can be adjusted with a screw-
driver once the case lid has been removed. The set
switching point can be checked through the inspec-
tion glass.
Switching point can adjusted with a screwdriver.
Protection class
IP 40 according to EN 60529
IP 65 according to EN 60529 (TZ 404)
IP 20 according to EN 60529
Electrical connection
Cable gland M 20 x 1.5,
for cable
∅ 6-12 mm
Cable connection directly on
terminals
Probe line-Ø
Approx. 2.4 mm (or 9.5 mm with 1.8 m capillary)
Case mounting
Wall mounting / pipe mounting
Wall mounting,
DIN rail installation TH35 according to DIN EN 60715
Weight
Approx. 0.2 kg
Allowable storage tempera-
ture
-30 °C to +80 °C
Allowable
ambient conditions
on the switching head
-20 °C to +80 °C
The ambient temperature must exceed the switching point by +2 °C.
Maximum allowable
probe line temperature
120 °C
Allowable minimum bending
radius of the probe line
20 mm
Electrical contact
Snap-action switch with single-pole changeover contact
Switching capacity
STW
STB
On the N/C contact (contact deck 1-2):
AC 230 V +10 %, 16 (2.5) A, cos
ϕ = 1 (0.6),
DC 230 V +10 %, 0.25 A
On the N/C contact (contact deck 1-2):
AC 230 V +10 %, 16 (2.5) A, cos = 1 (0.6),
DC 230 V +10 %, 0.25 A
On the N/O contact (contact deck 1-4):
AC 230 V +10 %, 6.3 (2.5) A, cos
ϕ = 1 (0.6),
DC 230 V +10 %, 0.25 A
On the signal contact (contact deck 1-4):
AC 230 V +10 %, 2 (04) A, cos = 1 (0.6),
DC 230 V +10 %, 0.25 A
Electrical connection
contact (plug-type terminal)
"Push-In
®
" terminal technology: Patented connection technology from Weidmüller GmbH & Co. KG, Detmold.
Connection cross section
0.75 to 2.5 mm
2
finely stranded (single-wire, fine wired with ferrule)
Switching reliability
To ensure high switching reliability, we recommend a minimum load of:
AC / DC = 24 V, 100 mA with silver contacts
Switching point accuracy
+/- 2 °C
Switching differential
1.5 +/- 1 °C