beautypg.com

3 installation, 2 approved process connections – JUMO 60.2026 Panel-mounting thermostat, EM Operating Manual User Manual

Page 11

background image

11

3 Installation

3.3.2

Approved process connections

Temperature
probe

10

Screw-
connections

50, 52, 54, 60, 65

Sheaths

20, 21, 22, 23, 24, 40, 41, 42

3.3.3

Sheath made of steel 22, 23, 32, 41, 42 and 45

Material

Capacity

max. admissible
operating
temperature

H

refer to data sheet 606710 !

Tube

Screw-in nipples

Welding nipples

St 35.8 I

Steel 1.0038

Steel 1.5415

Temperature

Pipe diameter

8 x 0.75 mm or

conical

10 x 0.75 mm

15 x 0.75 mm

Maximum admissible pressure

100 °C

89 bar

72 bar

48 bar

150 °C

83 bar

67 bar

45 bar

200 °C

78 bar

63 bar

42 bar

300 °C

59 bar

47 bar

32 bar

350 °C

50 bar

40 bar

27 bar

Tube

Nipple

max. admissible operating temperature*

static load

without load

St 35.8 I

Screw-in nipples

+300 °C

+530 °C

Welding nipples

+450 °C

* observe the max. admissible probe temperature of the respective thermostat version.

For operating temperatures > +420 °C: observe the operating life of 200,000 h at a static
load TRD508. Sheath "21" (UO) and "31" (UZO): Use only in pressureless medium.