Technical data
Analog inputs
General information
Thermocouples
RTD temperature probe
Number 4
A/D converter
Dynamic resolution up to 16 bit
Designation
Standard
Measuring range
Measuring accuracy
a
a
The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced linearization accuracy.
Ambient
temperature influence
Fe-CuNi “L”
-200 to +900 °C
0.1 % from -100 °C
300 ppm/K
Fe-CuNi “J”
DIN EN 60584
-200 to +1200°C
0.1 % from -100 °C
300 ppm/K
Cu-CuNi “U”
-200 to +600 °C
0.1 % from -130 °C
300 ppm/K
Cu-CuNi “T”
DIN EN 60584
-200 to +400 °C
0.1 % from -150 °C
300 ppm/K
NiCr-Ni “K”
DIN EN 60584
-200 to +1372 °C
0.1 % from -80 °C
300 ppm/K
NiCr-CuNi „E“
DIN EN 60584
-200 to +1000 °C
0.1 % from -80 °C
300 ppm/K
NiCrSi-NiSi “N”
DIN EN 60584
-100 to +1300 °C
0.1 % from -80 °C
300 ppm/K
Pt10Rh-Pt “S”
DIN EN 60584
-50 to 1768 °C
0.15 % from 20 °C
300 ppm/K
Pt13Rh-Pt “R”
DIN EN 60584
-50 to 1768 °C
0.15 % from 20 °C
300 ppm/K
Pt30Rh-Pt6Rh “B”
DIN EN 60584
0 to 1820 °C
0.15 % from 400 °C
300 ppm/K
W5Re-W26Re „C“
0 to 2320 °C
0.15 % from 500 °C
300 ppm/K
W3Re-W25Re “D”
0 to 2495 °C
0.15 % from 500 °C
300 ppm/K
W3Re-W26Re
0 to 2400 °C
0.15 % from 500 °C
300 ppm/K
Chromel-Copel
GOST 8.585-2001
-200 to +800 °C
0.15 % from -80 °C
300 ppm/K
Chromel-Alumel GOST
8.585-2001
-200 to +1372 °C
0.10 % from -80 °C
300 ppm/K
PLII (Platinel II)
0 to 1395 °C
0.10 % from -80 °C
300 ppm/K
Linear
0 to 75 mV
0.1 %
300 ppm/K
Cold junction
Pt100 internal
Cold junction accuracy
1 K
Designation
Standard
Measuring range
Measuring accuracy
a
Ambient
temperature influence
Pt100
DIN EN 60751
-200 to +850 °C
50 ppm/K
2-wire circuit
0.15 %
3-wire/4-wire circuit
0.05 %
Pt500
DIN EN 60751
-200 to +850 °C
50 ppm/K
2-wire circuit
0.30 %
3-wire/4-wire circuit
0.15 %
Pt1000
DIN EN 60751
-200 to +850 °C
50 ppm/K
2-wire circuit
0.20 %
3-wire/4-wire circuit
0.08 %
Ni 100
DIN 43760
-60 to +250 °C
50 ppm/K
2-wire circuit
0.36 %
3-wire/4-wire circuit
0.24 %
Pt100
JIS 1604
-200 to +650 °C
50 ppm/K
2-wire circuit
0.20 %
3-wire/4-wire circuit
0.06 %