HYDAC ETS 1700 User Manual

Page 8

background image

8.2 Summary of the basic settings

Setting

Display

Setting
range

Pre-
setting

Switching direction relay 1 (Relay 1)

”ON”: The relevant relay is activated when the

switching point is reached, and deactivated
when the temperature falls below the switch-
back point.

”OFF”: The relevant relay is activated in the

quiescent state (0 °C / 32 °F), and deactivated
when the switching point is reached.

ON/ OFF

ON

Switch-on delay relay 1 (Ton 1)

Time in seconds which must elapse, once the
particular switching point has been reached or
exceeded, before switching will occur.

0..900s

0.1

Switch-off delay relay 1 (Toff 1)

Time in seconds which must elapse, once the
temperature has fallen below the particular switch-
back point, before switching will occur.

0..900s

0.1

:
Relays 2..4 as above

Switch-back mode (Switch Mode)

”R.S.P”: The ETS 1700 operates with adjustable

switch-back points.

”HYST”: The ETS 1700 operates with adjustable

hystereses.

(see also point 6.1 "Relay outputs”)

R.S.P./
HYST.

HYST.

Primary display (Primary)

Display value which should remain permanently in the
display:

”ACT.”: current

temperature

”S.P.1” .. ”S.P.4”: switching point 1..4
”MAX”:

maximum value

ACT/
S.P.1 ..
S.P.4/
MAX

ACT.

Determining the display range (RANGE)

”°C”:

The temperature is displayed in °C.

”°F”:

The temperature is displayed in °F.

“FREE”: The display range can be defined by the

user. If this setting is selected, then
decimal places and upper and lower
display range must be set. (see below)

°C/ °F /
FREE

°C

Display the unit (Unit)

If set to ”YES” the pre-set unit will be displayed briefly
every 7 seconds.

YES/ NO

NO