HYDAC EDS 8000 User Manual
Page 8
User manual EDS 8000 US
Page 8
Status 09.09.2009
HYDAC ELECTRONIC GMBH
Part No. 669820
Example for switch output 1 (normally closed and normally open function):
Abbreviations:
"FH1", "FH2" = upper switch value 1 / upper switch value 2
"FL1", "FL2"
= lower switch value 1 / lower switch value 2
"FNO"
= normally open when window function is active
"FNC"
= normally closed when window function is active
NOTE
:
• It is only possible to set the switch point (SP) if it is higher than the respective
switch-back point (RP). In the case of low SPs we recommend setting the RP
first.
•
The window function only works properly (switching on and off) if all switch
values (including the safety margin) are above 0 bar and below the nominal
pressure range.
6.2
Setting ranges for the switching outputs
Measuring
range
Lower limit of
RP / FL
Upper limit of SP
/ FH
Min. difference
between
RP and SP or
FL and FH
Increment
in psi
in bar
in psi in bar
in psi
in bar
in psi
in bar
in psi in bar
0 .. 500 0.. 25
5
0,25
500
25
5
0,25
1
0,05
0 ..1000 0.. 40
10
0,40
1000
40
10
0,40
2
0,10
0 ..3000 0 ..100
30
1,00
3000
100
30
1,00
5
0,20
0 ..6000 0 ..250
60
2,50
6000
250
60
2,50
10
0,50
0 ..9000 0 ..400
90
4,00
9000
400
90
4,00
20
1,00
0
..600
6,00 600 6,00
1,00
* All ranges given in the table can be adjusted by the increments shown.
Rückschaltwert
Schaltwert
Schaltwert
Rückschaltwert
Sicherheitszone
Sicherheitszone
Ein
Aus
FL1 minus 0,4%FS
FL1
FH1
t
P
Ein
Ein
Aus
Aus
Ein
Aus
FNO
FNC
Schlie
ßerfunktion
Ö
ffnerfunktion
Rückschaltwert
Schaltwert
Schaltwert
Rückschaltwert
Sicherheitszone
Sicherheitszone
Ein
Aus
FL1
FH1
t
P
Ein
Ein
Aus
Aus
Ein
Aus
FNO
FNC
Schlie
ßerfunktion
Ö
ffnerfunktion
FH1 plus 0,4%FS
On
Normally open function
Off
On
Normally closed function
Off
Reverse switch point
Switch point
Switch point
Reverse switch point
Safety zone
Safety zone
Off
On
On
Off