EUCHNER ESM-BL2xx User Manual
Emergency stop safety relay esm-bl2, User information
1
User Information
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]
Emergency Stop Safety Relay ESM-BL2..
•
2 start behaviors possible:
- Manual start
- Automatic start
•
Short circuit and earth fault monitoring
•
Up to PL d, SILCL 2, category 3
•
It is not allowed to open the device, tamper with the de-
vice or bypass the safety devices.
•
All relevant safety regulations and standards are to be
observed.
•
The overall concept of the control system in which the
device is incorporated must be validated by the user.
•
Failure to observe the safety regulations can result in
death, serious injury and serious damage.
Correct Use
ESM-BL2.. is the low-cost emergency stop safety relay with which
machines and systems can be safely switched off by disconnect-
ing the power supply. Internal fault monitoring takes place
during restarting via the start button.
Applications for the ESM-BL2.. include single or dual-channel
emergency stop circuits and guard monitoring on machines and
systems.
Features
•
2 safe, redundant relay outputs
•
Connection of:
- Emergency stop buttons
- Safety switches
- Non-contact safety switches
•
Single and dual-channel operation possible
•
Feedback loop for monitoring downstream contactors or
expansion modules
•
Cyclical monitoring of the output contacts
•
Indication of the switching state via LED
Function
The emergency stop safety switching device ESM-BL2.. is
designed for safe isolation of safety circuits according to
EN 60204-1 and can be used up to safety category 3, PL d
according to EN ISO 13849-1.
The internal logical system closes the safety contacts when
the start button is pressed.
When the safety switch is opened, the positively driven
safety contacts are opened and safely switch the machine
off. It is ensured that a single fault does not lead to a loss of
the safety function and that every internal fault is detected
by cyclical self-monitoring no later than when the system is
switched off and switched on again. Only a fault in the
safety switch itself is not detected. This must be checked
regularly as part of a maintenance plan.
Electrical
Connection
•
When the 24 V version is used, a safety transformer
according to EN 61558-2-6 or a power supply unit with
electrical isolation from the mains must be connected.
•
External fusing of the contacts (4 A slow-blow or 6 A
quick-action or 10 A gG) must be provided.
•
A maximum length of the control lines of 1000 meters
with a line cross section of 0.75 mm
2
must not be ex-
ceeded.
•
The line cross section must not exceed 2.5 mm
2
.
•
If the device does not function after commissioning, it
must be returned to the manufacturer unopened. Open-
ing the device will void the warranty.
Installation
As per EN 60204-1, the device is intended for installation in
control cabinets with a minimum degree of protection of
IP54. It is mounted on a 35-mm DIN rail according to DIN
EN 60715 TH35.
Safety
Precautions
•
Installation and commissioning of the device must be
performed only by authorized personnel.
•
Observe the country-specific regulations when installing
the device.
•
The electrical connection of the device is only allowed to
be made with the device isolated.
•
The wiring of the device must comply with the instruc-
tions in this user information, otherwise there is a risk
that the safety function will be lost.
Fig. 1 Block diagram ESM-BL2..
Fig. 2 Installation / removal
Fig. 3 Connections
A1:
Power supply
A2 :
Power supply
S11:
DC 24V control voltage
S21:
Control line
13-14:
Safety contact 1
23-24:
Safety contact 2
(not for plug-in terminals)