Nozzle pressure, Electrical supply, Verify burner components – Beckett CF800 User Manual

Page 6: Vent system

background image

6

the fuel unit (oil pump) on the burner. Refer to fuel unit

literature in the literature envelope in the burner carton to

verify allowable suction pressure.

If fuel supply is level with or higher than fuel unit —

When the fuel unit is not required to lift the oil, the

installation is usually suitable for either a one-pipe or

two-pipe oil system. The oil pressure at the inlet of the

fuel unit must not exceed 3 psig.

Refer to the Mount the Burner Section of this manual for

one-pipe or two-pipe fuel supply installation instructions.

If fuel supply is below the fuel unit —

Use a two-pipe oil system when the fuel unit must lift the

oil more than 8 feet if burner is equipped with a B fuel

unit. The return line provided by the two-pipe system is

needed to purge the air from the fuel lines and minimize

the likelihood of air-related problems during operation.

Nozzle Pressure

The fuel unit nozzle port pressure is factory set at 140
psig. Some original equipment manufacturer burner
applications may call for a lower pressure to obtain a
required fi ring rate. Do not change this pressure unless
directed to do so by the appliance manufacturer.

Electrical Supply

Verify that the power connections available are correct
for the burner. Refer to Figure 1. All power must be
supplied through fused disconnect switches.

Verify Burner Components

Burner, Model CF500 or CF800

Air tube assembly

Mounting fl ange kit

Oil nozzle, per Table 1 — Only 45° to 70° solid pattern
nozzles are recommended unless otherwise specifi ed
by appliance manufacturer. (See specifi c appliance
recommendation sheet or refer to OEM Spec Guide).
Find the required fi ring rate in the 140 psig column
(factory-set fuel unit pressure). Select the corresponding
nozzle from column 1 (Rated gph @ 100 psig).

Vent System

Figure 1. Typical Nameplate

Correct Nozzle and Flow
Rate Required

Incorrect nozzles and fl ow rates could

result in impaired combustion, under-

fi ring, over-fi ring, sooting, puff-back of

hot gases, smoke and potential fi re or

asphyxiation hazards.

Use only nozzles having the brand, fl ow rate (gph),

spray angle and pattern specifi ed by the appliance

manufacturer. Follow the appliance manufacturer’s

specifi cations for the required pump outlet pressure for

the nozzle, since this affects the fl ow rate.

y

Nozzle manufacturers calibrate nozzle fl ow rates at
100 psig.

y

This burner utilizes pressures higher than 100 psig,
so the actual nozzle fl ow rate will be greater than the
gph stamped on the nozzle body. (Example: A 2.00
gph nozzle at 140 psig = 2.37 gph.

y

For typical nozzle fl ow rates at various pressures
see Table 1.

Section: Pre-installation Checklist

Table 1 - Nozzle Capacities

Rated gph @ 100

psig

Pressure - Pounds per square inch

140

150

1.75

2.07

2.14

2.00

2.37

2.45

2.25

2.66

2.74

2.50

2.96

3.06

2.75

3.24

3.37

3.00

3.55

3.68

3.50

4.13

4.29

4.00

4.70

4.90

4.50

5.30

5.51

5.00

5.90

6.13

5.50

6.50

6.74

6.00

7.10

7.33

6.50

7.65

7.96

The fl ue gas venting system must be in good condition
and must comply with all applicable codes.

LISTED

(FUEL) BURNER

SERIAL NUMBER

050214-00000

Control Circ: 120V/60Hz 4.5A

Motor Circ: 120V/60Hz 4.0A

Model “XX”

Series (Fuel) Burner

For use with Group 8 . . .

MP 1192 XX000 R00

X
X
X
X
X
X

XX000 R00

050214-00000

MFR’S SETTINGS

R.W. Beckett Construction & Setting Data

R.W. Beckett Specifi cation
Number and Revision

Boiler Manufacturer and
Model, When Applicable

Additional Codes

General Model Information

Serial Number,Including Date Code

Rating Information

Approval Agency Symbols

Primary Group and Fuel

L0002