1. STANDBY. The burner is idle, waiting for a call for

heat. When a call for heat is initiated, there is a 3-10
second delay while the control performs a safe start
check.

2. VALVE-ON DELAY. The ignition and motor are turned

on for a 15 second valve-on delay.

3. TRIAL FOR IGNITION (TFI). The fuel valve is opened.

A fl ame should be established within the 15 second
lockout time.

4. LOCKOUT. If fl ame is not sensed by the end of the

TFI, the control shuts down on safety lockout and must
be manually reset. If the control locks out three times
in a row, the control enters restricted lockout.

5. IGNITION CARRYOVER. Once fl ame is established,

the ignition remains on for 10 seconds to ensure fl ame
stability before turning off. If the control is wired for

Typical Burner Sequence of Operation - R7184P Control.

Refer to the appliance manufacturer’s wiring diagram for actual specifi cations.

Control

Model

Features

Interrupted

ignition

Limited reset,

Limited recycle

Valve-on

delay

Burner motor

off delay

Alarm

Contacts

R7505A

YES

YES

Optional

R7505B

YES

YES

YES

Optional

R7505P

YES

YES

YES

YES

Optional

R7184A

YES

YES

R7184B

YES

YES

YES

R7184P

YES

YES

YES

YES

Optional

Table 6 - Control System Features

Section: Wire the Burner

intermittent duty ignition, the ignition unit stays on the
entire time the motor is running.

6. RUN. The burner runs until the call for heat is satifi ed.

The burner is then sent to burner motor off delay, if
applicable, or it is shut down and sent to standby.

7. RECYCLE. If the fl ame is lost while the burner is

fi ring, the control shuts down the burner, enters a 60
second recycle delay, and then repeats the above
ignition sequence. If fl ame is lost three times in a row,
the control locks out to prevent cycling with repetitious
fl ame loss due to poor combustion.

8. BURNER MOTOR-OFF DELAY. The fuel valve is

closed and the burner motor is kept on for the selected
motor-off delay time before the control returns the
burner to standby.

2

1

3

5

6

8

4

7

Standby

Motor-off delay

Valve-on delay

Trial for
ignition

Ignition carryover

Run

Lockout

Recycle