Series, Save these instructions, Circuit lighting track – Altman Lighting Track Lighting: GLOBALtrac tec 2-circuit / 2-neutral track system User Manual
Page 2

2-circuit Lighting Track
with independent neutrals
INSTALLATION INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
When installing or using this track system, basic safety precautions should always be
followed, including the following :
1. Read all of these installation instructions before installing the GLOBAL tek lighting track
system
2. The GLOBAL tek track system is intended for use only with GLOBAL tek components and
fixtures marked for use with GLOBAL tek system. To reduce risk of fire and electric
shock, do not use other components as part of this system.
3. Track installation is to only be performed by a certified electrician in accordance with the
National Electrical Code and all local codes and ordinances.
4. The GLOBAL tek system is designed to be fed by two branch circuits rated 120VAC, 20A,
eg. the system is a two-circuit / two-neutral track and care must be taken to keep circuits
designated as circuit1 and circuit2 separate.
5. Do not install the track in damp or wet locations.
6. Do not install any parts of the track system less than 5 ft above the floor.
7. Do not install any fixtures closer than six inches from combustible materials.
8. Do not use this track with a power supply cord or convenience receptacle adapter.
9. Do not install the track with electric power connected. Similarly, disconnect electricity
when installing or removing fixtures or components or changing the configuration of the
track.
10. Do not attempt to energize anything other than Lighting Track Fixtures on the track. To
reduce the risk of fire and electrical shock, do not attempt to connect power tools,
extension cords, appliances and the like to the track.
SAVE THESE INSTRUCTIONS
series
Installation instructions D1974e