Rbs alarms and flash codes, Resetting the rbs controller, Maintenance schedule – JLG M400 Service Manual Service Manual User Manual
Page 111: Rbs alarms and flash codes -69
SECTION 3 - CHASSIS & TURNTABLE
3121827
– JLG Lift –
3-69
RBS Alarms and Flash Codes
In the event of an RBS alarm, a flash code will be issued
and an alarm indicated on the analyzer.
Alarms must be reset once the fault has been corrected
(see below).
Resetting the RBS Controller
The RBS can be reset using the analyzer or by disabling
and re-enabling the RBS controller. This will clear any cur-
rent fault condition with the controller.
Maintenance Schedule
Check oil level every 24 hours
Change engine oil and filter every 150 hours
Table 3-10. RBS Alarms and Flash Codes
Flash Code
Problem
RBS Condition
1-1
Low Oil Pressure
1
Below 7psi
Shutdown
1-2
High Engine Temp.
Over248°F(120°C)
Shutdown
1-3
Overspeed
Over 3800 RPM
Shutdown
1-4
Underspeed 1
Below 2000 RPM
Shutdown
Overcrank
3 failed crank cyclesCall to start removed
Call to start removed
1-5
No Speed Signal
2
Shutdown
2-1
Overvoltage
3
Over 63VDC
Shutdown
2-2
Engine Starting System fault 4
Alarm
2-4
Loss Of Voltage Sense
Alternator output less than 1/2 of the system
nominal voltage (58VDC)
Shutdown
steady
Unit Enabled, no faults
Unit can respond to any call to start
-
Unit Off / Disabled
Unit will not respond to any call to start
Notes:
1 Enabled once time delay bypass period has elapsed after engine startup.
2 Delayed to ensure the fault was not momentary.
3 Measured at the alternator output, shutdown is delayed by a factory set period to ensure the fault was not caused by a transient condition.
4 Indicates a problem with the engine start battery, engine magneto or magneto-voltage regulator.