Section 7, To remove end covers – Hale SMR-U User Manual
Page 15

 
 
Section 7
PRIMING SYSTEMS
POSITIVE DISPLACEMENT PISTON PRIMERS
 
 
To Remove End Covers 
 
Access to each identical primer, mounted on each side of the bearing housing, is as 
follows: 
 
The primer end cover contains a priming valve and inlet and outlet valves and is 
removed by the removal of 4 nuts and washers (see Fig 8-1). 
Servicing of this cover is as follows 
Primer end cover
Inlet seal, 
Orifice plate 
Outlet seal 
Cylinder 
assembly 
Priming valve
Fig 8-1 Piston Primer
After removal of a single central M8 socket cap screw, the inlet seal, orifice plate and 
outlet seal may be removed. Replacement or reassembly may follow after applying 
Loctite 262 to the screw thread. Note this screw must be tightened to ensure that 
the rubber seal is compressed until metal to metal resistance is achieved. 
 
The priming valve mounted above may be stripped as follows – remove the 4 M6 
bolts (and washers) which pass through the end cover into the inlet casting (which 
contains an O ring in the bore) and an O ring face seal to the end cover. 
 
The outer end cap clamps on to a rubber diaphragm against the main cover. The 
priming valve now revealed has a single socket screw and Nyloc nut to constrain its 
components. 
©Godiva, Warwick 
September 2000 
wsmaint-Issue2 25-9-02 
15