Mounting Guidelines

The Model 01917 Automatic Transfer Switch is enclosed in a
NEMA Type 1 enclosure suitable for indoor use only. The
Model 01918 Automatic Transfer Switch is enclosed in a
NEMA Type 3R enclosure suitable for indoor/outdoor use.

Guidelines for mounting the Automatic Transfer Switch
include:

• Model 01918 Automatic Transfer Switch must be

installed with minimum NEMA 3R hardware for conduit
connections.

• Install the switch on a firm, sturdy supporting

structure.

• To prevent switch contact distortion, level and plumb

the enclosure. This can be done by placing washers
between the switch enclosure and the mounting
surface.

• Never install the switch where any corrosive substance

might drip onto the enclosure.

• Protect the switch at all times against excessive

moisture, dust, dirt, lint, construction grit and corrosive
vapors.

The typical installation of the Automatic Power Transfer
Switch is depicted below. Discuss layout
suggestions/changes with the owner before beginning the
system installation process.

Power Wiring Interconnections

All wiring must be the proper size, properly supported, of
approved insulation qualities, and protected by NEC
approved conduit.

Complete the following connections between the generator,
transfer switch and main distribution panel (shown on next
page).

1. Connect utility power supply leads from a two pole

breaker installed in the main distribution panel to
transfer switch terminals marked “UTILITY
CONNECTION”. Use a 50 Amp circuit breaker. Ensure
breaker is turned OFF.

2. Connect main distribution panel ground to the transfer

switch “GND” bus.

3. Connect main distribution panel neutral lead to transfer

switch “NEUTRAL” terminal.

4. Connect generator power supply leads from the

generator’s control panel to transfer switch terminals
marked “GENERATOR CONNECTION”.

5. Connect generator Neutral from the control panel to the

transfer switch “NEUTRAL” terminal.

6. Connect generator “GND” from the control panel to the

transfer switch “GND” terminal.

7. Connect generator utility 240V terminals to transfer

switch utility 240V terminals.

8. Tighten all wire connections/fasteners to proper torque.

7

WARNING

Low voltage wire cannot be installed in same
conduit as power voltage wiring.

• Failure to follow above warning could cause personal injury,

damage and/or malfunction of equipment.

Automatic

Transfer Switch

Main

Distribution

Panel