Troubleshooting

Problem

Cause

Correction

Automatic transfer switch does not
transfer to generator

1. Generator breaker open.

2. Generator voltage not acceptable.

1. Reset generator circuit breaker.

2. Refer to generator manual.

Automatic transfer switch does not
transfer to utility

1. Utility disconnect circuit breaker

open.

2. Utility voltage not acceptable.

1. Reset utility disconnect circuit

breaker.

2. Wait for utility voltage to return to

normal.

Generator is still running after switch
transfers to utility power

Engine cool down period.

Engine should stop after 1 minute.

Generator is still running after utility
power is restored

1. Minimum engine run time has not

elapsed.

2. Fuse(s) in transfer switch is

defective.

1. Wait five minutes for transfer

switch to retransfer to utility power.

2. Check fuse(s) and replace if

necessary.