beautypg.com

Bryant 619CNF User Manual

Page 10

background image

—10—

VI. STEP 6 — MAKE ELECTRICAL CONNECTIONS

Be sure field wiring complies with local building codes and
NEC, and unit voltage is within limits shown in Table 5.

Contact local power company for correction of improper line
voltage.

NOTE: Use copper wire only between disconnect switch(es)
and unit.

NOTE: Install branch circuit disconnect of adequate size to
handle unit starting current per NEC. Locate disconnect
within sight of, and readily accessible from, unit, per Section

440-14 of NEC. Some codes allow indoor unit to share discon-
nect with outdoor unit if disconnect can be locked; check
local code before installing in this manner.

1. Route ground and power wires.

2. Route line power leads (see Fig. 16) from indoor

disconnect to the fan coil unit. Place wire through
hole on the control box (Fig. 17). Connect wire to high
voltage terminal board (TB1) and ground screw.
When routing the wire in the unit, use care to keep
the wire away from refrigerant and condensate
piping and any sharp edges. The 208/230-v units are
factory wired for 230-v to 24-v transformer operation.
For 208-v to 24-v operation, interchange blue (208-v)
and red (230-v) wires. Cap any unused wires with
wire nuts.

Table 5 — Electrical Data*

LEGEND

*All units are 208/230-1-60. Minimum operating voltage is 187, maxi-

mum is 253. Units will operate satisfactorily within this voltage range.

†Electrical data is the same for both the 24,000 Btuh 024 unit and the

024 unit that has been field-reconfigured for 18,000 Btuh. Refer to
Before Installation section on page 3 for reconfiguration details.

WARNING: To avoid personal injury or damage to

unit, do not make electrical connections until all power
sources are shut down, locked out, and tagged off.
Failure to do so could result in personal injury or unit
damage.

CAUTION: Operation of unit on improper line volt-

age constitutes abuse and could affect warranty. Refer
to Table 5 for permissible operating limits. Do not
install unit in system where voltage may fluctuate
above or below permissible limits.

WARNING:

According to NEC and most local

codes, the unit must have an uninterrupted, unbroken
ground to minimize personal injury if an electric fault
should occur. The ground may consist of electrical wire
or metal conduit when installed in accordance with
existing electrical codes. Failure to follow this warning
could result in an electric shock, fire, or death.

SYSTEM

TYPE

UNIT

SIZE

FAN

HEATER

POWER

MIN WIRE SIZE

(AWG)

Motor 1 FLA

Motor 2 FLA

kW

FLA

MCA

MOCP

FLA

COOLING
ONLY

024†

0.5

0.53

15

0.50

14

036

1.3

1.60

15

1.30

14

048

1.1

0.5

2.00

15

1.60

14

060

1.3

1.3

3.30

15

2.60

14

HEAT PUMP

024†

0.5

2.00

8.66

9.29

15

9.16

14

036

1.3

3.00

13.00

17.70

20

14.30

14

048

1.0

0.5

4.00

17.40

23.80

25

19.00

12

060

1.3

1.3

5.00

21.70

28.70

30

24.30

10

AWG

American Wire Gage

FLA

Full Load Amps

MCA

Minimum Circuit Amps per NEC Section 430-24

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

This manual is related to the following products: