Table 33 — Fan Performance 580F072,073 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*
LEGEND
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied
drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See below for general fan performance notes.
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 9 — Motor Data for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
919
0.63
561
1010
0.75
663
1095
0.87
771
1174
1.00
886
1250
1.14
1008
1900
960
0.73
648
1047
0.85
754
1129
0.98
867
1206
1.11
986
1279
1.25
1111
2000
1001
0.84
744
1085
0.96
855
1163
1.09
972
1238
1.23
1095
1309
1.38
1224
2100
1043
0.96
850
1123
1.09
965
1199
1.22
1086
1271
1.37
1213
1340
1.52
1346
2200
1085
1.09
966
1162
1.22
1086
1235
1.36
1211
1305
1.51
1342
1372
1.67
1479
2300
1127
1.23
1092
1201
1.37
1217
1272
1.52
1347
1340
1.67
1482
1405
1.83
1623
2400
1169
1.38
1229
1241
1.53
1359
1310
1.68
1493
1375
1.84
1633
1439
2.00
1778
2500
1212
1.55
1378
1281
1.70
1513
1348
1.86
1652
1412
2.02
1796
1473
2.19
1945
2600
1255
1.73
1539
1322
1.89
1678
1386
2.05
1822
1448
2.22
1970
1508
2.39
2124
2700
1298
1.93
1713
1363
2.09
1857
1425
2.26
2005
1485
2.43
2158
1544
2.61
2315
2800
1341
2.14
1899
1404
2.31
2048
1464
2.48
2201
1523
2.66
2358
1580
2.84
2520
2900
1384
2.36
2099
1445
2.54
2253
1504
2.71
2410
1561
2.90
2572
—
—
—
3000
1428
2.60
2313
1487
2.78
2471
—
—
—
—
—
—
—
—
—
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1321
1.28
1137
1390
1.43
1273
1455
1.59
1415
1518
1.76
1563
1579
1.93
1718
1900
1348
1.40
1243
1415
1.56
1381
1479
1.72
1526
1541
1.89
1677
1601
2.06
1834
2000
1377
1.53
1359
1442
1.69
1500
1505
1.86
1648
1565
2.03
1801
1624
2.21
1961
2100
1406
1.67
1485
1470
1.83
1629
1531
2.00
1780
1591
2.18
1936
1648
2.36
2098
2200
1437
1.83
1621
1499
1.99
1769
1559
2.16
1923
1617
2.34
2082
1673
2.53
2246
2300
1468
1.99
1769
1529
2.16
1920
1587
2.34
2077
1644
2.52
2239
1699
2.71
2406
2400
1500
2.17
1928
1559
2.35
2083
1616
2.53
2243
1672
2.71
2408
1726
2.90
2579
2500
1533
2.36
2098
1591
2.54
2257
1647
2.73
2421
—
—
—
—
—
—
2600
1566
2.57
2281
1623
2.75
2444
—
—
—
—
—
—
—
—
—
2700
1600
2.79
2477
—
—
—
—
—
—
—
—
—
—
—
—
2800
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2900
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
3000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Bhp
— Brake Horsepower Input to Fan