beautypg.com

Communication and status function lights, Defrost – Bryant EVOLUTIONR EXTREME 280ANV User Manual

Page 9

background image

9

Crankcase Heater Operation

This unit has an internal crankcase heater that will be energized

during the off cycle and is intelligently demanded by the system to
prevent the compressor from being the coldest part of the system

thus enhancing the reliability. The crankcase heater will function
as needed any time the outdoor unit is powered. The indoor unit

and UI do not need to be installed for the crankcase heater to
operate properly.
NOTE:

Contactor may close intermittently without the unit

starting. This is done to determine whether the control needs to
energize the crankcase heater. Closing the contactor powers the
inverter and allows the system to check compressor temperature.

Outdoor Fan Motor Operation

The outdoor unit control (Fig. 11) energizes outdoor fan anytime
compressor is operating, except for defrost and as needed during

low--ambient cooling operation. The outdoor fan remains
energized if a pressure switch opens or compressor scroll over

temperature should occur. This OD fan is an ECM motor which

operates at varying speeds depending on the ambient and the
demand.

Time Delays

The unit time delays include:

S

Five minute time delay to start cooling or heating operation when

there is a call from the user interface. To bypass this feature,

momentarily short and release Forced Defrost pins.

S

Five minute compressor re--cycle delay on return from a

brown--out condition.

S

See Table 7 for other delay information.

General Information

Evolution Controlled low ambient cooling:

This unit is capable of low ambient cooling down to 0°F (--17.8°C)

with Low Ambient enabled on the Evolution Control. A low
ambient kit is not required. The only accessory that may be

required is wind baffles in locations which are likely to experience
cross winds in excess of 5 miles an hour. This generally occurs

only on roof and open area applications. The Evolution Control
provides an automatic evaporator freeze thermostat. Low ambient

cooling must be enabled in the User Interface setup. Fan may not

begin to cycle until about 40°F (4.4°C) OAT. Fan will cycle based

on coil and outdoor air temperature.
Evolution controlled low ambient mode operates as follows:

S

Fan is OFF when outdoor coil temperature is too low (+

55_F/12.7_C), the saturated suction pressure indicates a freezing

indoor coil or outdoor fan has been ON for 30 minutes. (Fan is

turned off to allow refrigerant system to stabilize.)

S

Fan is ON when outdoor coil temperature is too high

(+80_F/26.7_C), the high side pressure is too high or if outdoor

fan has been OFF for 30 minutes. (Fan is turned on to allow

refrigerant system to stabilize)

S

Low pressure indication by the suction pressure transducer is

ignored for first 3 minutes during low ambient start up. After 3

minutes, if low pressure trip occurs, then outdoor fan motor is

turned off for 10 minutes, with the compressor running. If

pressure condition is satisfied within 10 minutes then cooling

continues with the outdoor fan cycling per the coil temperature

routine listed above for the remainder of the cooling cycle. If the

suction pressure condition is not satisfied within 10 minutes, then

the normal trip response (shut down cooling operation and

generate LP trip error) will occur.

Utility Interface With Evolution Control

The utility curtailment relay should be wired between the two

UTIL connections on the control board for this Evolution
Communicating System (see Fig. 20). This input allows a power

utility device to interrupt compressor operation during peak load
periods. When the utility sends a signal to shut the system down,

the User Interface will display, ”Curtailment Active”. See UI
installation instructions for setup details.

Communication and Status Function Lights

Evolution Control, Green Communications (COMM)Light
A green LED (COMM light) on the outdoor board (see Fig. 11)

indicates successful communication with the other system

products. The green LED will remain OFF until communication is
established. Once a valid command is received, the green LED will

turn ON continuously. If no communication is received within 2
minutes, the LED will be turned OFF until the next valid

communication.
Amber Status Light
Amber colored STATUS light indicates operation and error status.

See Table 7 for definitions.

S

Two minute time delay to return to standby operation from last

valid communication.

S

One minute time delay of outdoor fan at termination of cooling

mode when outdoor ambient is greater than or equal to 100_F

(37.8_C).

S

Fifteen second delay at termination of defrost before the auxiliary

heat is de--energized.

CB

MODEL

PL8

FORCED

DEFROST

J2

1

BRN

RED

SEC1

SEC2

PWM2

PWM1

INVER

TER

PL1

PL2

RVS

CC

PL11

PL4

PL6

OCT

OAT

SPT

OST

A B C NO

USE

UTIL

LS Y

C

O

COMM STATUS

YEL

BLU

EXV

PL5

PL3

HPS

A12048

Fig. 11 -- Variable Speed Control Board

Defrost

This user interface (UI) offers 5 possible defrost interval times: 30,
60, 90, 120 minutes, or AUTO. The default is AUTO.
Defrost interval times: 30, 60, 90, and 120 minutes or AUTO are

selected by the Evolution Control User Interface (dip switches are
not used.)
AUTO defrost adjusts the defrost interval time based on the last
defrost time as follows:

S

When defrost time <3 minutes, the next defrost interval=120

minutes.

S

When defrost time 3--5 minutes, the next defrost interval=90

minutes.

S

When defrost time 5--7 minutes, the next defrost interval=60

minutes.

S

When defrost time >7 minutes, the next defrost interval=30

minutes.