beautypg.com

Caution – Bryant EVOLUTIONR EXTREME 280ANV User Manual

Page 6

background image

6

Outdoor Unit Connected to Factory--Approved Indoor

Unit

Outdoor unit contains correct system refrigerant charge for

operation with factory--approved, AHRI--rated smallest indoor unit

when connected by 15 ft. (4.57 m) of field--supplied or

factory--accessory tubing, and factory--supplied filter drier. Check
refrigerant charge for maximum efficiency.
NOTE: If the indoor furnace coil width is more than the furnace
casing width, refer to the indoor coil Installation Instructions for
transition requirements.

Install Liquid--Line Filter Drier Indoor

Refer to Fig. 6 and install filter drier as follows:

1. Braze 5--in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5--in. (127 mm) liquid tube.
4. Connect and braze liquid refrigerant tube to the filter drier.

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage or

improper operation.
Installation of filter drier in liquid line is required.

Factory Supplied Muffler (part # LM10KK003)

Installation is Required On Every Installation:

S

A muffler is required to reduce noise transmitted to indoor through

the line set.

S

Muffler must be installed outside the dwelling. Muffler can also be

installed in vertical configuration for space consideration

maintaining a minimum of 12 in (304.8 mm) straight pipe section

to the closest bend.

S

Maintain at least 12 in. (304.8 mm) straight pipe length to the

muffler shell inlet and from the outlet stubs.

S

To prevent rusting, provide sufficient clearance between the

muffler and the ground surface. Also, position the muffler such that

accidental abuse (such as by a weed trimmer, lawn mower etc.) of

the painted surface is avoided. Apply touch--up paint to muffler

braze joints.

S

Insulating the muffler with Armaflext tape is recommended.

EXTERIOR
WALL

VAPOR LINE

MUFFLER

TO DWELLING

A12044

Fig. 5 -- Muffler Installation

A05227

Fig. 6 -- Liquid--Line Filter Drier

Refrigerant Tubing connection Outdoor

Connect vapor tube to fitting on outdoor unit vapor service valves
(see Table 1).

NO Installation of Adapter Tube

Although it is a heat pump this unit has a standard AC liquid

service valve. An EXV inside the unit serves as the heating
expansion device.

Sweat Connections

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
S

Use a brazing shield

S

Wrap service valves with wet cloth or heat sink material.

Use refrigerant grade tubing. Service valves are closed from factory
and ready for brazing. After wrapping service valve with a wet

cloth, braze sweat connections using industry accepted methods
and materials. Consult local code requirements. Refrigerant tubing

and indoor coil are now ready for leak testing. This check should

include all field and factory joints.

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the

recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used. See Service Manual for

triple evacuation method. Always break a vacuum with dry
nitrogen prior to opening the refrigerant system for servicing.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of

pulling a vacuum of 500 microns and a vacuum gauge capable of
accurately measuring this vacuum depth. The deep vacuum method

is the most positive way of assuring a system is free of air and

liquid water. (See Fig. 7)