Step 14 — pumpdown & evacuation, Pump down – Bryant EVOLUTIONR EXTREME 280ANV User Manual
Page 11

11
0
50
100
150
200
250
300
350
400
0
10
20
30
40
50
60
Vapor Service
Valve Pressure
Suction Pressure
For use in Heating Charging Mode only
Heating Check Chart - 280ANV024/036
See user interface set in Charging Mode
Charging In Cooling Mode - 280ANV024/036
(-18ºC)
(-12ºC)
(-10ºC)
(-7ºC)
(4ºC)
(10ºC)
(16ºC)
Outdoor Ambient Temperature ºF (ºC)
Refrigerant Pressure (psig)
Refrigerant Pressure (KPa)
2757
2413
2068
1724
1380
1034
690
345
0
80ºF ID (27ºC)
70ºF ID (21ºC)
60ºF ID (16ºC)
A12045
280ANV024/036 Heating Pressure check Chart (Psig)
OD DB
(_F)
Indoor Temperature (_F)
60
70
80
High
Low
High
Low
High
Low
60
290
129
329
130
368
132
50
263
106
303
108
346
110
40
245
89
285
90
324
90
30
232
74
270
81
312
87
20
222
69
256
68
291
64
10
212
55
246
52
281
53
0
203
49
238
43
270
50
Fig. 12 -- Heating Pressure Check Chart 280ANV024/036
Heating Check Chart - 280ANV048/060
0
50
100
150
200
250
300
350
400
450
0
10
20
30
40
50
60
Vapor Service
Valve Pressure
Suction Pressure
Charging In Cooling Mode - 280ANV048/060
For use in Heating Charging Mode only
See user interface set in Charging Mode
80ºF ID (27ºC)
70ºF ID (21ºC)
60ºF ID (16ºC)
(-18ºC)
(-12ºC)
(-10ºC)
(-7ºC)
(4ºC)
(10ºC)
(16ºC)
Outdoor Ambient Temperature ºF (ºC)
Refrigerant Pressure (psig)
Refrigerant Pressure (KPa)
2757
2413
2068
1724
1380
1034
690
345
0
3102
A12046
280ANV048/060 Heating Pressure check Chart (Psig)
OD DB
(_F)
Indoor Temperature (_F)
60
70
80
High
Low
High
Low
High
Low
60
324
121
360
120
407
121
50
293
99
333
100
380
102
40
277
87
307
80
360
88
30
257
69
288
65
333
69
20
242
57
281
60
320
60
10
232
50
263
47
306
50
0
218
42
253
43
288
42
Fig. 13 -- Heating Pressure Check Chart 280ANV048/060
Step 14 — Pumpdown & Evacuation
If this system requires either a Pump Down or Evacuation for any
reason, the procedures below must be followed:
Pump Down
Because this system has an inverter controlled, compressor, suction
pressure transducer and EXV, conventional procedure cannot be
used to “pump down” and isolate the refrigerant into the outdoor
unit. The UI (User Interface) has provisions to assist in performing
this function.
1. Connect gages to 280ANV liquid and vapor or suction ca-
pillary service ports to monitor operating pressures during
and at completion of the procedure.
2. In the advanced menu of the UI, go to Checkout > Heat
Pump> Pumpdown
3. Select mode to pump down in (COOL or HEAT), COOL
mode allows refrigerant to be isolated in outdoor unit.
HEAT mode allows the refrigerant to be isolated in indoor
coil and lineset. Set desired time period. Default time peri-
od for the procedure is 120 minutes.
4. Select Start on UI to begin the pumpdown process. Unit
will begin running in selected mode after a brief delay.
5. Close the liquid service valve.
6. The unit will run in selected mode with the low pressure
protection set to indicate pumpdown is complete when the
suction pressure drops below 0 psig. Compressor protec-
tions are still active to prevent damage to the compressor or
inverter (high pressure, high current, high torque, scroll
temperature, etc.) .
7. Once system indicates pumpdown complete or failure to
complete shutdown, close vapor service valve.
8. If pumpdown does not complete due to compressor safety
shutdown, a recovery system will be required to remove fi-
nal quantity of refrigerant from indoor coil and line set.
9. Remove power from indoor and heat pump unit prior to ser-
vicing unit.
NOTE: A small quantity of charge remains in the OD unit that
must be manually recovered if isolating refrigerant to indoor coil
and lineset via HEAT mode PUMP DOWN.
Evacuation and Recovery of Refrigerant from within
280ANV
Because this system has an EXV for the heating expansion device,
additional steps must be taken to open the EXV if the heat pump
unit must be evacuated for service reasons. If the EXV is not open
when pulling a vacuum or recovering refrigerant from the heat
pump unit, extended evacuation time may be required and/or
inadequate vacuum obtained.
The UI (User Interface) has
provisions to open the EXV for refrigerant recovery and/or
evacuation.
1. Connect gages to 280ANV liquid and vapor or suction ca-
pillary service ports to monitor operating pressures during
and at completion of the procedure. Attach recovery system
or vacuum pump to gage set as needed for the service pro-
cedure. The service valves must be open to evacuate the
unit through the line set service ports. The suction capillary
service port is a direct connection to the suction port of the
compressor.
2. In the advanced menu of the UI, go to Checkout > Heat
Pump> > Evacuation.
3. Set desired time period. Default time period for the proced-
ure is 120 minutes.
4. Select START on UI to open the valve.
5. Begin evacuation or refrigerant recovery as required for the
procedure after UI indicates the EXV is open. Power may
be removed from heat pump after the UI indicates “READY
TO EVACUATE.”
6. Remove power from indoor and heat pump unit prior to ser-
vicing unit. The EXV will retain the open position.
NOTE: See service training materials for troubleshooting the
EXV using EXV CHECK mode.