6 720 607 909

Installation instructions

21

Recommended exhaust vent terminator position

Fig. 21

* Subject to local codes and anticipated snow level

** Other equipment that operates with a mechanical air inlet may require greater distances, reference manufacturer's instructions

NOTICE: Exhaust and air intake must always be located
on the same wall to cancel wind pressure effects.

Ref.

Description

Minimum distance

A

Directly below an opening; operable windows, doors and any non-
mechanical fresh air openings

36 in (twin pipe installation)

48 in (single pipe installation)

B

Below a gutter, sanitary pipework or eaves

24 in

Below a gutter, sanitary pipework or eaves, protected by metal
shielding

12 in

C

From any internal corner

12 in

D*

Above ground or snow pack

12 in

Above a paved sidewalk

7 ft

E

From an opposing wall or structure facing the termination

24 in

From the relief valve of a Ip gas regulator

36 in

F

From a terminator facing a terminator

48 in

G

Vertically between two exhaust vent terminators on the same wall

60 in

H

Horizontally between two exhaust vent terminators on the same wall

12 in

I**

Horizontally and vertically from the combustion air inlet terminator

36 in

From the gravity combustion air inlet any other equipment

48 in

J

From any external corner

12 in

K

Horizontally from an opening; operable windows, doors and any non-
mechanical fresh air openings

12 in

L

From wall on exhaust applications

10 in

Table 10