beautypg.com

Bosch PROTANKLESS GWH 345/450 ESR User Manual

Page 17

background image

6 720 607 909

Installation instructions

17

Use table below to define which restrictor to be used.

After installation is complete, check CO

2

levels per

chapter 3.9.

Combustion air inlet connection

The combustion air inlet accessory can only be
connected to the top right of the appliance. The left side
must remain sealed.
Note: Before installing the combustion air inlet
accessory, the appropriate inlet air restrictor must
be determined using Tables 6, 7 and 8.
Refer to Fig. 15 for mounting sequence.

B Place gasket, deflector, gasket and inlet air restrictor

on the air inlet opening lining up screw holes as seen
in Fig. 15.

Fig. 15 Mounting sequence

a

Gasket

b

Deflector

c

Restrictor

d

Adaptor

B Attach the combustion air inlet accessory (8 705

504 141) to the top of the unit (position 3) using the
4 screws provided.

B Install 3" combustion air pipe over the air inlet

accessory. If using flexible piping, secure with a
clamp (position 4, not included).

Fig. 16 Exhaust air inlet accessory

Total equivalent length (ft)

Restrictor Ø

GWH3

45

NG

20 - 38

38

38 - 78

40

GWH450

NG

18 - 28

44

28 - 40

47

40 - 65

50

65 - 78

55

Total equivalent length (ft)

Restrictor Ø

GWH345

LP

G

20 - 38

38

38 - 78

40

G

W

H

450 LPG

18 - 28

47

28 - 50

50

50 - 78

55

Table 8 Restrictors table