Vent Piping

1. Do not exceed maximum vent lengths. Refer to

Table 4.

2. Installation of a vertical vent tee 8116304U is

required on all vertical vent applications. See

Figures 6 and 7. Attach vertical vent drain tee

directly to elbow or horizontal pipe from an elbow

immediately after vent connector.

3. Slope horizontal runs minimum ¼ inch per foot.

Slope towards vertical vent drain tee. Position weld

seams in vent pipes, in all horizontal runs, at the top

to avoid condensate from lying on the seams.

4. Install fire stops where vent passes through floors,

ceilings or framed walls. The fire stop must close

the opening between the vent pipe and the structure.

5. Whenever possible, install vent straight through

the roof. Refer to Figure 7 if offset is necessary.

E.

Vertical Venting System

- See Figures 6, 7 and 8.

Maintain minimum clearance to combustible

materials.

6. Install Vent Terminal.

a. Size roof opening to maintain minimum

clearance from combustible materials.

b. Extend vent pipe to maintain minimum vertical

and horizontal distance of twelve (12) inches

from roof surface. Allow additional vertical

distance for expected snow accumulation.

Provide brace as required. Refer to Figure 8.

c. Install storm collar on vent pipe immediately

above flashing. Apply Dow Corning Silastic 732

RTV Sealant between vent pipe and storm collar

to provide weathertight seal.

d. Attach vent terminal.

NOTICE

Roof penetrations require the use of roof flashing

and storm collar - not supplied with boiler.